SNMP exporter

Purpose

kubernetes/apps/observability/snmp-exporter polls SNMP devices that have no native Prometheus exporter: the core switch, the two MikroTik switches, the APC rack PDUs, and the Brother printer fleet. Each device family gets its own scrape target and, where the device needs one, a custom snmp_exporter module in a dedicated ConfigMap.

Why the core switch is two scrape targets

if_mib (port counters and status) and entity_sensor (temperature, fan, PSU, optics) are scraped as separate targets rather than one target running both modules. A scrape is only as healthy as its slowest module. Measured against the switch on 2026-08-27, 8 walks each through the exporter's own /snmp endpoint:

Walk Success rate Avg time Max time
if_mib alone 8/8 0.3s 1.9s
entity_sensor alone ⅝ 11.3s 20.1s
both together 4/8 11.0s 20.1s

Combined, that marked the whole target down about 29% of the day, so up read "core switch unreachable" while its interface data was in fact fast and complete, and the critical SnmpTargetDown alert was one slightly longer stall away from paging on it. Split, if_mib stays a trustworthy reachability signal and a slow sensor walk can no longer forge an outage. The same split, for the same reason, is why the MikroTik switches are each two targets (health/PoE vs interfaces); see device & infrastructure monitoring for that measurement.

MikroTik module: what is not hardcoded

mtxrHealthTable is self-describing (column .2 is the sensor name, .3 the reading, .4 a unit code), and which sensors exist differs by model, so the set of sensors is not hardcoded in the ConfigMap. Observed unit codes are 1=celsius, 2=rpm, 6=state (boolean). Codes 3/4/5 appear on voltage/current/power rows respectively, but the exact scaling factor has not been confirmed against the device CLI, so nothing in the module or its alerts assumes one.

mtxrPOETable carries the port's own name in column .2, so the per-port device label is looked up from the switch at scrape time rather than written into this public repository.

PoE-based device monitoring: alert design

Devices with no exporter, agent or probe of their own (access points, a Zigbee coordinator) are watched through the switch's own PoE meter instead; see device & infrastructure monitoring for why that signal is reliable here. Two implementation choices in MikrotikPoeDeviceLostPower:

  • It compares mtxrPOEPower against zero, not the mtxrPOEStatus enum. The status enum's meaning was inferred from observation, not from a MIB the exporter holds, so an alert built on it would encode a guess. Zero-versus-nonzero needs neither the enum nor the unconfirmed power scaling factor.
  • The lookback term is max_over_time, not min_over_time. The rule has to answer "was this port ever powered recently", and min_over_time answers "was it powered at every sample", which breaks the rule two ways: a single zero during the reboot window the for: 15m exists to tolerate would blank the evidence for the next 6h and suppress a real outage in that period, and during a sustained outage the first zero enters the 6h offset window after about 30 minutes, so the alert would resolve itself roughly 15 minutes after firing while the device was still dead. With for: 15m and no further activity, the alert self-resolves about 6.5 hours after the device is unplugged.

Scrape-health alerts are a failure rate, not up == 0

OnyxSensorScrapeDegraded and MikrotikInterfaceScrapeDegraded both fire on 1 - avg_over_time(up[1h]) > 0.5 rather than up == 0 with a long for:. The walks they cover fail intermittently in short bursts, mostly under 5 minutes, which never trips a for: clause. Before this rule shape existed, the equivalent combined target flapped about 130 times a day while going completely unalerted. Writing the expression as 1 - avg_over_time(...) rather than comparing the success rate directly means $value in the alert is the failure fraction the summary quotes; avg_over_time(up) alone is the success fraction, so the direct form would understate how often the walk is actually failing.